The tank shall be located and operated so that the
(a) temperature of the oil in the tank does not exceed 38 °C (100°F);
(b) horizontal distance from the tank to any fuel-fired appliance, other than a combustible-fuel-oil-driven internal combustion engine, is not less than 0.6 m (2 ft), except when approved as part of an appliance or as permitted by Clause 7.4.9; and
(c) tank installation does not interfere with the required working space of any electrical panel or apparatus. A minimum working space of 1 m with secure footing shall be provided.